All data overview

ProfiMessage / ProfiLab

Module type

ADVT / AAST / ADIT

ADGT

AMDT / ADFT  

Analog inputs
Sensorsmv, mA, Thermocouples, RTD (RTD except ADVT)mv, mA, Thermocouples, RTD mV, mA
Voltage and current measurement range± 156 mV .. ± 10 V / 0 .. 20 mA, 4 .. 20 mA
Galvanic isolation to system750 VDC
Galvanic isolation channel to channel110 V650 V100 V
Resolution24 bit24 bit14 bit
Measurement accuracy

V / mA: 0.01 % from upper range value (URV)

 

Pt100: 0.1 K

 

Pt1000: 0.05 K

 

Thermocouples: 0.1 % URV

V / mA: 0.01 % from upper range value (URV)

 

Pt100: 0.1 K

 

Pt1000: 0.05 K

 

Thermocouples: 0.1 % URV
± 1.25 V .. ± 10 V: ± 0.1 % URV
± 0.625 V: ± 0.2 % URV
± 0.312 V: ± 0.3 % URV
± 0.156 V: ± 0.4 %URV
Analog outputs

Resolution

16 bit-12 bit
Galvanic isolation750 V-100 V
Output0/4 .. 20 mA-0 .. 10 V
Max. burden / min. load650 Ω-2.5 kΩ
Digital inputs
Galvanic isolation2.5 kV
Input measurement rangelow: 0 .. 1.5 VDC@0 .. 1.5 mA / high: 3.5 .. 90 (ProfiLab: 50) VDC@2 mA
Frequency / counter inputs
Galvanic isolation /
input measurement range
2.5 kV / low: 0 .. 1.5 VDC@0 .. 1.5 mA / high: 3.5 .. 90 (ProfiLab: 50) VDC@2 mA
Measurement frequencyup to 30 kHz (DIOT), up to 50 kHz (AMDT, ADFT)
Digital outputs
Potential isolation2.5 kV
Switching voltagemax. 50 VDC@2.5 A
Data storage
Internal2 .. 14 GB (approx. 40 million measurement values per GB / 300 million measurement values per GB for AMDT, ADFT)
Interfaces
Physical equipment
COM 1 / COM 2
RS485, 9-pole sub-D-socket, DIN EN ISO 19245-1
Physical equipment
COM 3 / COM 4
RS232, 9-pole sub-D-plugs
Protocols COM 1 / COM 2PROFIBUS DPV1 Slave (both interfaces), incl. redundancy according to PNO 2.212 V1.2
Protocols COM 1 .. COM 4Modbus RTU master / slave, customer-specific protocols, ASCII
EthernetRJ45 (8-pole STP-socket), 100Base-TX; Protocols: TCP/IP, HTTP, SMTP, NTP, Modbus TCP and OPC UA Client / server
USBUSB 1.1. for configuration and data memory read out
CAN9-pole sub-D-socket, Protocols: CAN, RAW; baud rates: 50 k .. 1 MBaud
Module bus
Mechanical type3-pole Phoenix connector; internal bus to connect additional modules
Baud rate / length1 MBaud (adjustable) / up to 10 m
General technical information
ProfiMessage dimension / weight200 x 73 x 118 mm  / 1 kg
ProfiMessage fixingRail mounting DIN EN 60715 or screw fixing
ProfiMessage signal connectionsDetachable screw terminals, 33 terminals in 2 rows, lead protection, connecting cabling max. 2.5 mm²
ProfiLab dimension W 226 x H 145 x D 180 mm
ProfiLab signal connectionsUp to 64 4 mm lab sockets, gold-plated
Temperature range-20 .. 50 °C
Power supply12 .. 36 VDC / 12 .. 28 VAC eff. / ± 10 %
Power input< 10 Watt

Registered: 14.03.2019